Enable and configure analog inputs
Connect Tank has four analog inputs, each of which you can configure as either a 4-20 mA current loop or a voltage input. For details about the configuration options, see Analog Current Loop Input and Voltage Input option definitions.
To set analog input options:
- Sign in to Remote Manager.
- Click the arrow next to your user name and choose Open Classic Remote Manager.
- Click Device Management > Devices tab.
- Double-click the Connect Tank device you want to configure.
- Expand the Configuration menu.
- Select the analog input for your sensor:
- Analog: 4-20mA Current Loop 1-4
- Analog: Voltage Input 1-4
Note Configure each analog input as either a current loop or a voltage input, not both. For example, if you enable Analog: 4-20mA Current Loop 1, make sure you disable Analog: Voltage Input 1.
- Enable the input by selecting On for Interface Enable.
- Select On for the alarms you want to enable and enter an appropriate value for each threshold that you enabled. For more information, see Alarms.
- Enter a value for Hysteresis to prevent multiple alarms when the sensor input value is near a high or low threshold. For more information, see Hysteresis.
- Enter a user-friendly name that describes the sensor in the Sensor Description field.
- Enter the unit of measurement type, such as inches, that you are using for your application in the Custom Scaled Sample Unit field.
- Enter the sensor manufacturer's values for y1 and y2 in the Custom Scaled Sample Value fields. For more information about the Custom Scaled fields, see Custom scaled sensor values.
- Enable the oversampling feature, if desired. For more information about this feature, see Oversampling.
- From the Oversampling (ovs) list box, select the option that describes the desired value for the sampled data: Average, Minimum, or Maximum.
- In the Oversampling Inter-sample Delay field, specify the time interval between readings. The time is measured in milliseconds.
- In the Oversampling Number Samples field, specify the number of data samples that must be taken.
-
Apply the configuration changes:
- Click Save > Schedule. The Save Device Properties dialog appears.
- Select Immediate.
- Select Schedule Offline.
- Click Schedule. Connect Tank downloads and applies configuration changes the next time it connects to Remote Manager.