Analog Current Loop Input and Voltage Input option definitions
The following table provides Remote Manager definitions for Connect Tank Analog: 4-20mA Current Loop and Analog: Voltage Input options. For additional information about using these options, see Enable and configure analog inputs.
Option | Description |
Range |
Default |
---|---|---|---|
Interface Enable | Enables or disables the analog input source. | On/Off | Off |
High Alarm |
Enables or disables high alarm reports for the analog input source. |
On/Off | Off |
High Threshold |
Specifies the input value that generates a high alarm report when High Alarm is On. |
|
Current loop: 20.0 mA Voltage: 10.0 volts |
Low Alarm | Enables or disables low alarm reports for the analog input source. | On/Off | Off |
Low Threshold |
Specifies the input value that generates a low alarm report when Low Alarm is On, in the following units: Current Loop inputs — mA Voltage inputs — volts |
|
Current loop: 4.0 mA Voltage: 0.0 volts |
Delta Low Alarm | Enables or disables delta low alarm reports for the analog input source. | On/Off | Off |
Delta Low Threshold |
Specifies the input value that generates a delta low alarm report when Delta Low Alarm is On. |
|
Current loop: 16.0 mA Voltage: 10.0 volts |
Delta High Alarm | Enables or disables delta high alarm reports for the analog input source. | On/Off | Off |
Delta High Threshold |
Specifies the input value that generates a delta high alarm report when Delta High Alarm is On. |
|
Current loop: 16.0 mA Voltage: 10.0 volts |
Hysteresis |
Specifies the input value to keep an alarm on or shut off an alarm during high and low alarm states. 0 — hysteresis is off 1 or more — hysteresis is on and managing alarms |
|
Current loop: 1.0 mA Voltage: 1.0 volts |
Sensor description | Specifies description of the sensor for this input source. | Text | Empty |
Custom Scaled Sample Unit | Specifies the unit of measurement this analog input is using for the custom scaled sensor values. | Text | Empty |
Custom Scaled Sample Value (y1) |
Specifies the first data point associated with the following raw value: Current Loop inputs — 4 mA Voltage inputs — 0 volts |
Number | 0 |
Custom Scaled Sample Value (y2) |
Specifies the second data point associated with the following raw value: Current Loop inputs — 20 mA Voltage inputs — 10 volts |
Number | 0 |
Oversampling (ovs) |
Enables or disables oversampling. The feature is enabled when you specify how the readings should be manipulated:
|
Off Average Minimum Maximum |
Off |
Oversampling inter-sample Delay (ovi) | The time interval at which a sample is taken. | 0 - 5000 milliseconds | 50 |
Oversampling Number Samples (ovn) | The number of samples that should be taken. | 2 - 100 | 10 |