Analog Current Loop Input and Voltage Input option definitions

The following table provides Remote Manager definitions for Connect Tank Analog: 4-20mA Current Loop and Analog: Voltage Input options. For additional information about using these options, see Enable and configure analog inputs.

Option Description

Range

Default
Interface Enable Enables or disables the analog input source. On/Off Off
High Alarm

Enables or disables high alarm reports for the analog input source.

On/Off Off
High Threshold

Specifies the input value that generates a high alarm report when High Alarm is On.

  • Current loop: 4.0 - 22 (mA)
  • Voltage: 0.0 - 10.5 (volts)

Current loop: 20.0 mA

Voltage: 10.0 volts

Low Alarm Enables or disables low alarm reports for the analog input source. On/Off Off
Low Threshold

Specifies the input value that generates a low alarm report when Low Alarm is On, in the following units:

Current Loop inputs — mA

Voltage inputs — volts

  • Current loop: 4.0 - 22 (mA)
  • Voltage: 0.0 - 10.5 (volts)

Current loop: 4.0 mA

Voltage: 0.0 volts

Delta Low Alarm Enables or disables delta low alarm reports for the analog input source. On/Off Off
Delta Low Threshold

Specifies the input value that generates a delta low alarm report when Delta Low Alarm is On.

  • Current loop: 4.0 - 22 (mA)
  • Voltage: 0.0 - 10.5 (volts)

Current loop: 16.0 mA

Voltage: 10.0 volts

Delta High Alarm Enables or disables delta high alarm reports for the analog input source. On/Off Off
Delta High Threshold

Specifies the input value that generates a delta high alarm report when Delta High Alarm is On.

  • Current loop: 4.0 - 22 (mA)
  • Voltage: 0.0 - 10.5 (volts)

Current loop: 16.0 mA

Voltage: 10.0 volts

Hysteresis

Specifies the input value to keep an alarm on or shut off an alarm during high and low alarm states.

0 — hysteresis is off

1 or more — hysteresis is on and managing alarms

  • Current loop: 4.0 - 22 (mA)
  • Voltage: 0.0 - 10.5 (volts)

Current loop: 1.0 mA

Voltage: 1.0 volts

Sensor description Specifies description of the sensor for this input source. Text Empty
Custom Scaled Sample Unit Specifies the unit of measurement this analog input is using for the custom scaled sensor values. Text Empty
Custom Scaled Sample Value (y1)

Specifies the first data point associated with the following raw value:

Current Loop inputs — 4 mA

Voltage inputs — 0 volts

Number 0
Custom Scaled Sample Value (y2)

Specifies the second data point associated with the following raw value:

Current Loop inputs — 20 mA

Voltage inputs — 10 volts

Number 0
Oversampling (ovs)

Enables or disables oversampling. The feature is enabled when you specify how the readings should be manipulated:

  • Average: An average of all of the readings taken. This is the recommended option.
  • Minimum: The minimum value of all of the readings taken.
  • Maximum: The maximum value of all of the readings taken.

Off

Average

Minimum

Maximum

Off
Oversampling inter-sample Delay (ovi) The time interval at which a sample is taken. 0 - 5000 milliseconds 50
Oversampling Number Samples (ovn) The number of samples that should be taken. 2 - 100 10