Configure analog inputs and power outputs for a Connect Sensor
Connect Sensor has four analog inputs, each of which you can configure as either a 4-20 mA current loop or a voltage input.
Analog power outputs
You can enable and configure the analog power output options when you use Connect Sensor to power analog sensors. Each of the four analog inputs also has four corresponding power outputs to power sensors. The analog power outputs work independently: each one powers only its corresponding analog input.
When Connect Sensor powers multiple sensors, it powers only one sensor at a time for each sensor reading. This also allows you to set different voltage ranges for each power output.
-
Log into the Connect Sensor web UI from Digi Axess.
-
In the Interfaces section, click Analog I/O.
-
Configure the analog inputs: Analog 1, Analog 2, Analog 3, and Analog 4. Information about the fields is in the table below.
-
Click Update to save your changes.
Option | Description |
---|---|
Input |
Determine the analog input type. Options are:
|
Oversampling |
Select the option that describes the desired value for the sampled data. Options are:
See Oversampling for a feature description. Note Reading a large number of data samples over a long interval reduces battery life. |
Oversampling Delay | Specify the time interval between oversampling readings. The time is measured in milliseconds. |
Oversampling count | Specify the number of data samples that must be taken. |
High send trigger |
Specify whether you want to generate a high trigger report. Options are:
|
High trigger |
Specifies the input value that generates a high alarm report when the high trigger is enabled. |
Low send trigger |
Specify whether you want to generate a low trigger report. Options are:
|
Low trigger | Specifies the input value that generates a low alarm report when the low trigger is enabled. |
Hysteresis |
Specifies the input value to keep an alarm on or to shut off an alarm during high and low alarm states.
See Hysteresis for more information. |
Power output |
Enables or disables the power output source. Options are:
|
Output voltage |
Specifies the voltage level output for the power source. The default is 3.3 Volts. |
Read delay |
Specifies the time in seconds that the sensor voltage is enabled before Connect Sensor reads its value. This allows the sensor to stabilize to get an accurate reading. The default is 0. Note A higher read delay keeps the device powered on longer, which reduces battery life. |