16 Port Multi-Function I/O module
Characteristics
This module type is configured for communication with Digi's 16-Port Multi-Function I/O Modules. They consist of 8 physical inputs and 8 physical outputs. Inputs may be defined as data type digital, analog, or pulse through the Automation Control application. Outputs are of type digital.
Communications
Digi's 16-port multi-function I/O module uses 2-wire RS485 communications with a proprietary protocol. Appropriate settings are all pre-configured on TR2-/TR2+ (pins 15 & 16) of the Z45 Controller.
Addressing
Addresses for 16-port I/O modules are hexadecimal numbers between 1 and FF. Modules are shipped from the factory with a default address of 99.
Resetting an Unknown Address
To address a module with an unknown address perform the following steps
-
Disconnect all I/O modules except for the one having the unknown address.
-
Enter the text “default” for the address of the first physical (16-port) Multi-Function I/O module on the screen.
-
Click Save. The connected module is given the address of "99" by default.
-
Change the address of the target module to the desired address.
-
Click Save.
Note If multiple modules are connected during the default addressing described above, all will be set to address 99.
Replacing a 16-port Multi-Function I/O module
To replace an I/O module while retaining its current configuration perform the following steps
-
Remove the module to be replaced from the RS485 string.
-
Remove any module on the RS485 string having the address of 99.
-
Connect the new (replacement) module to the string.
-
Assign an address of 99 to that module.
-
Click Save.
-
Assign the desired address to that module.
-
Click Save.
-
Reconnect previously disconnected modules.